
FCC Information
This is a Class A product. When used domestically, this device may cause interference to communications equipment. Users are advised to take appropriate protective measures.
This product has been tested and shown to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this manual, it may cause harmful interference to radio communications. Operation in a residential area may require the user to correct interference at their own expense.
RoHS Information
This product complies with RoHS requirements.
Safety Information
![]() |
Caution symbol. Refer to the cautions and instructions in this manual to avoid personal injury or equipment damage. |
![]() |
Electric shock hazard symbol. High voltage may be present inside this product; do not touch. The equilateral triangle containing a lightning bolt and arrowhead warns users that uninsulated dangerous voltage is present inside the product enclosure and may be of sufficient magnitude to pose a risk of electric shock. |
![]() |
Chassis ground symbol. |
Warning: To reduce the risk of fire or electric shock, do not expose this equipment to rain or moisture. Dangerous high voltage is present inside the enclosure. Do not open the enclosure. Servicing must be performed by qualified personnel only.
Important Safety Instructions
Strictly follow all warnings and operating instructions in this manual and on the device. Keep this manual in a safe place. Do not operate this device until you have read all safety and operating instructions.
Set the maximum over-current protection for the power circuit according to the rated current information on the device label. Follow all applicable national regulations, safety codes, and breaker tolerance requirements.
Connect this device only to a properly grounded power outlet or grounded power system.
Ensure that the total output current of all connected equipment does not exceed the rated current shown on the device label.
Replacing the battery with an incorrect type may cause an explosion. Dispose of used batteries according to applicable regulations.
If the power supply is unstable, measurement results from this device may be inaccurate.
Do not use this device near water or in humid locations. To reduce the risk of fire or electric shock, do not expose this device to rain or moisture.
Clean only with a dry cloth.
Use only attachments and accessories specified by the manufacturer.
All servicing must be performed by qualified service personnel. Return the device for service if it is damaged in any way, for example:
The power cord or plug is damaged.
Liquid has been spilled or objects have fallen into the equipment.
The equipment has been exposed to rain or moisture and does not operate properly, or has been dropped.
Do not attempt to service this equipment yourself. Opening the enclosure may expose you to dangerous voltage or other hazards. Contact your dealer for assistance.
Do not allow objects or liquids to enter the equipment. Contact with hazardous voltage points or short circuits may cause fire or electric shock.
Refer to the safety symbols on the equipment enclosure.
No one except qualified service personnel should adjust or repair this equipment.
User Information
The manufacturer reserves the right to modify the information, documentation, and specifications contained in this manual without prior notice. The manufacturer makes no warranty, express or implied, regarding merchantability or fitness for a particular purpose, including any manufacturer software described in this manual.
If a defect in the software is discovered after purchase, the purchaser (not the manufacturer, distributor, or reseller) shall bear all necessary service costs, repair liability, and any incidental or consequential damages caused by software defects.
The manufacturer is not responsible for radio or television interference caused by unauthorized modification of this device; the user must correct such interference.
If the operating voltage is not configured correctly before use, the manufacturer is not liable for resulting damage. Always verify the voltage setting before operation.
The manufacturer warrants this product to the original end user for one (1) year from the date of purchase against defects in materials and workmanship. During the warranty period, subject to proof of purchase, defective products or components will be repaired or replaced at no charge for parts or labor, at the manufacturer's discretion, to restore normal operation. Replacement may be new or refurbished with equivalent or greater value, as determined by the manufacturer. This warranty does not apply to products that have been modified, misused, altered, damaged by disaster, or operated outside normal conditions.
This warranty does not apply to defects caused by installation or use by any third party (including customers or end users), negligent or improper operation, unauthorized modification, repair not performed according to the manufacturer's written instructions, normal wear, disassembly, connection to incompatible equipment or software, integration into systems not intended for this product, connection of incompatible hardware or software, computer networks containing viruses, modified or interrupted carrier networks, or repair by unauthorized personnel.
If your device does not operate properly, contact the service provider listed on the support and warranty card included with the product packaging.
Chapter 1 Product Introduction
1-1 Product Introduction
RPD-406 integrates switched outlet control, web-based management, event logging, email and SNMP notifications, and scheduling. IT staff can monitor outlet status and resolve power-related issues remotely over the network, reducing downtime and on-site visits.
1-2 Applications
Data center and server room equipment monitoring and management
Computer center power management for government and enterprise sites
Factory equipment power control
Network equipment power monitoring
Other power equipment monitoring and remote control applications
1-3 Features
Front-panel LEDs show the on/off state of each outlet.
Remote administrators can control outlets through a web browser, eliminating on-site visits.
Supports email and Pushover alert delivery.
Supports SNMP v1/v2c and v3 for network management integration.
Supports Syslog for centralized log collection.
Records user actions and alarm events for later review.
Provides remote firmware update.
Built-in overload circuit breaker protects connected equipment.
10/100 Mbps Ethernet management port.
1-4 Hardware Description

| 1 | Outlet status LEDs — LEDs 1–6 on the front panel; green indicates the corresponding outlet is energized |
|---|---|
| 2 | Circuit breaker — Over-current protection (front panel, right side) |
| 3 | Power switch — Main rocker power switch (I/O) |
| 4 | Power inlet — IEC C14 AC inlet (rear panel) |
| 5 | Outlets 1–6 — Six switched NEMA 5-15R outlets with locking mechanism (rear panel) |
| 6 | RESET — Pinhole factory-reset button (rear panel; use a straightened paper clip) |
| 7 | LAN — RJ45 Ethernet port for management (rear panel) |
1-5 Package Contents
![]() |
Remote power PDU × 1 |
| Power cord × 1 | |
| Quick start / warranty card × 1 |
If any items are missing or defective, contact your dealer within seven (7) days of purchase for replacement.
Chapter 2 Hardware Installation
2-1 Rack Mounting
RPD-406 fits standard 19-inch racks. Use the rack mounting accessories included in the package. Install the brackets on the unit first, then mount the assembly in the cabinet.
2-2 Product Installation
To ensure proper operation, follow these installation steps as shown in the diagram:

- Connect devices: Plug your servers or equipment into the output outlets (1–6) on the rear panel.
- Network connection: Connect a standard Ethernet cable to the LAN port for remote management.
- Power connection: Plug the supplied power cord into the power inlet, then into a grounded AC outlet.
Chapter 3 Initial Connection and Login
This chapter covers the steps required for first-time connection and Web UI login. Follow the flow for IP search, network connection, login, screen layout, and changing IP settings.
3-1 IP Search Utility
This section explains how to use the Java IP Search Utility on Windows, macOS, Linux, and other platforms to discover devices on the local network and change IP settings or DHCP mode. Because the utility uses UDP broadcast packets, it cannot find devices across routers.
Adapter: Select the network interface used to send search packets. Choose a NIC on the same subnet as the device (some Windows versions allow only one NIC for broadcast).
Product List
Discovered devices appear in the list. Field descriptions:
Product Model: Device model name.
Version: Firmware version.
DHCP: true means the IP is assigned by a DHCP server; false means a static IP.
IP Address: Current IPv4 address of the device.
Netmask: Device subnet mask.
Gateway: Device default gateway.
MAC: Device MAC address.
Http Open: true means the HTTP management interface is enabled.
Http Port: HTTP port (default 80).
Https Open: true means HTTPS is enabled.
Https Port: HTTPS port (default 443).
Configuration
After selecting a device in the product list, change network parameters below and apply:
DHCP: When checked, the device obtains an IP via DHCP; uncheck to enter IP fields manually.
IP: Set the device IPv4 address (when DHCP is off).
NetMask: Set the device subnet mask.
Gateway: Set the device default gateway.
MAC: Shows the selected device MAC address (read-only) for verification.
btn:gray:Refresh: Search again for devices on the local network and refresh the product list.
btn:gray:Configure: Write configuration to the selected device and reboot it. After reboot, click Refresh to read updated network information.
3-2 Network Connection
After connecting the network cable, the device obtains an IP address via DHCP (default 192.168.1.100 if no DHCP server is available). Discover the assigned IP with IP Search Utility (see 3-1 IP Search Utility).
3-3 Login
Navigation: Enter the device IP in a browser (when Show Device List is off), or select a device from the device list to open the login page.
Factory default credentials are admin / admin. On a new device or after factory reset, sign in with admin / admin and click btn:blue:Login.

Field Descriptions
Username: Enter an account with access permission; it must match a user defined under Permissions.
Password: Enter the password for the account. Repeated failures may lock the account or trigger password policy restrictions.
Remember Me: When checked, the browser keeps login information on the next visit; do not use on shared computers.
Button Descriptions
btn:blue:Login: Sign in when credentials are valid; first login may require a password change.
On a new device or after factory reset, the system requires a password change after successful login (subject to password policy). Set a new password and click btn:blue:OK to continue. Use the new password thereafter; the default admin password is no longer valid.

Field Descriptions
New Password: Enter the new login password; it must meet the password policy if enabled.
Confirm New Password: Re-enter the new password for confirmation; both entries must match.
Button Descriptions
btn:blue:OK: Submit the new password and complete first-login setup.
3-4 Web Interface
After login, select a menu item to open the working screen. The layout is described below:

Field Descriptions
User Bar: Shows the current locale and signed-in account.
Menus: The top bar is the main menu; the left sidebar lists sub-items for the selected menu; the right panel shows the selected page.
Main Panel: Shows monitoring values, forms, or lists for the selected menu—the main work area.
The following sections describe each menu in detail.
3-5 Change IP Settings
Navigation: System → Network.
If the device IP is assigned via DHCP and you need a different address, open System, then Network from the dropdown.

Field Descriptions
IPv4
DHCP: When enabled, IPv4 is assigned by the LAN DHCP server; disable to enter fields manually below.
MAC: Shows this device's Ethernet MAC address (read-only) for network management or ARP lookup.
IP Address: Sets the device IPv4 address; must match subnet and gateway; you may need to sign in again after changing it.
Subnet Mask: Sets the IPv4 subnet mask defining the LAN range (commonly 255.255.255.0).
Default Gateway: Sets the default IPv4 gateway, usually the router IP.
DNS Server 1: Primary DNS server for name resolution; use a reachable DNS server.
DNS Server 2: Secondary DNS server as backup when primary fails; may be blank.
IPv6
IPv6 Address: Sets the device IPv6 address; must match prefix length and gateway.
Prefix Length: Sets the IPv6 prefix length (commonly 64) defining the LAN range.
IPv6 Gateway: Sets the IPv6 default gateway for outbound traffic.
IPv6 DNS Server 1: Primary IPv6 DNS server address.
IPv6 DNS Server 2: Secondary IPv6 DNS server address; may be blank.
Button Descriptions
btn:gray:Cancel: Discards changes and restores values from when the page was opened.
btn:blue:Save: Saves and applies network settings; reconnect with the new address if the IP changed.
Chapter 4 Device Monitoring and Parameters
This chapter describes monitoring and configuration for outlets, schedules, ping monitors, and related settings.
4-1 Outlet
Shows outlet on/off state and allows direct switching from the web UI.
4-1-1 Monitoring Screen
Shows the power state of each outlet and allows direct switching from the web UI.

Field Descriptions
Outlets 1–6: Shows outlet name and index matching chassis and panel labels.
Power Icon: Shows outlet power state; green means energized. Click the icon to toggle the outlet.
Reboot: When checked, performs a power cycle (off then on) for remote device recovery.
4-1-2 Parameter Settings
The example below uses outlet 1 (Outlet1). Click the icon in the upper-right corner of the outlet tile to open parameter settings. All outlets use the same layout.

Field Descriptions
| Boot Type | Default outlet power state after device reboot or power restoration; choose Off, On, Reboot, or Last State from the dropdown.
|
| Boot Delay | Delay in seconds before energizing the outlet after device power-on. Set different values per outlet for sequential power-on to avoid simultaneous inrush overload. For example: outlet 1 = 0 s, outlet 2 = 30 s, outlet 3 = 60 s. |
| On Delay | Delay in seconds before energizing when turning the outlet on remotely. |
| Off Delay | Delay in seconds before de-energizing when turning the outlet off remotely. |
4-2 Schedule
Navigation: Control → Schedule.
This page creates scheduled tasks to run preset actions on devices or outlets at specified times. If Skip Holidays is checked, the schedule does not run on configured holidays.
Field Descriptions
Name: Schedule name for identification.
Schedule: Summary of run time or recurrence.
Action: Operation when the schedule fires (e.g., turn outlets on or off).
Target: Device, group, or outlets the schedule applies to.
Button Descriptions
btn:blue:Add: Opens the form to create a schedule.
btn:green:Running: Toggles whether the schedule runs. When Running, it fires at configured times; click to switch to Stopped and click again to resume.
btn:red:Delete: Deletes this schedule.
4-2-1 Add Schedule
Click btn:blue:Add to open the form below.
Field Descriptions
General
Name: Schedule name.
Action: Operation when the schedule fires (e.g., turn outlets on, off, or reboot).
Skip Holidays: When enabled, this schedule does not run on holidays.
Run Missed on Boot: Whether to run missed schedules after device reboot.
Schedule
Recurrence: How often the schedule repeats; choose from the dropdown. After selecting recurrence, matching time fields appear (hour, minute, weekday, day, month, etc.).
- Specific Date: Run yearly on the specified month, day, hour, and minute; list summary shows Yearly M/D HH:MM.
- Monthly: Run monthly on the specified day, hour, and minute.
- Weekly: Run weekly on the specified weekday, hour, and minute.
- Daily: Run daily at the specified hour and minute.
- Hourly: Run hourly at the specified minute.
Hour: Hour to run (0–23); hidden for Hourly recurrence.
Minute: Minute to run (0–59).
Weekday: Weekday for weekly runs; shown only for Weekly recurrence.
Day: Day of month for monthly or specific-date runs; shown for Monthly and Specific Date recurrence.
Month: Month for specific-date runs; shown only for Specific Date recurrence.
Targets
Select outlets this schedule applies to (Outlet1–Outlet6).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the schedule list.
btn:blue:Save: Saves the schedule and returns to the list.
4-2-2 Edit Schedule
Click an item in the list to open the edit screen.

Field Descriptions
General
Name: Schedule name.
Action: Operation when the schedule fires (e.g., turn outlets on, off, or reboot).
Skip Holidays: When enabled, this schedule does not run on holidays.
Run Missed on Boot: Whether to run missed schedules after device reboot.
Schedule
Recurrence: How often the schedule repeats; choose from the dropdown. After selecting recurrence, matching time fields appear (hour, minute, weekday, day, month, etc.).
- Specific Date: Run yearly on the specified month, day, hour, and minute; list summary shows Yearly M/D HH:MM.
- Monthly: Run monthly on the specified day, hour, and minute.
- Weekly: Run weekly on the specified weekday, hour, and minute.
- Daily: Run daily at the specified hour and minute.
- Hourly: Run hourly at the specified minute.
Hour: Hour to run (0–23); hidden for Hourly recurrence.
Minute: Minute to run (0–59).
Weekday: Weekday for weekly runs; shown only for Weekly recurrence.
Day: Day of month for monthly or specific-date runs; shown for Monthly and Specific Date recurrence.
Month: Month for specific-date runs; shown only for Specific Date recurrence.
Targets
Select outlets this schedule applies to (Outlet1–Outlet6).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the schedule list.
btn:blue:Save: Saves changes and returns to the list.
Delete
Click btn:red:Delete on the right of a list item to open a confirmation dialog.

btn:gray:Cancel: Closes the dialog without deleting.
btn:red:OK: Confirms deletion of this schedule.
4-3 Ping Monitor
Navigation: Control → Ping Monitor.
This page configures network reachability targets. The device periodically checks whether hosts or services are reachable; on failure, a preset action may run (e.g., outlet reboot).
Field Descriptions
Name: Monitor entry name.
Target Host: IP address or hostname to monitor.
Protocol: Protocol for monitoring (ICMP or TCP).
Run Command on Failure: Whether to run the preset command on failure.
Command: Action on failure (e.g., reboot outlet).
Target: Outlets the command applies to.
Button Descriptions
btn:blue:Add: Opens the form to add a monitor entry.
btn:green:Running: Toggles whether monitoring runs. When Running, checks run at the configured interval; click to switch to Stopped and click again to resume.
btn:red:Delete: Deletes this ping monitor entry.
4-3-1 Add Ping Monitor
Click btn:blue:Add to open the form below.
Field Descriptions
General
Name: Monitor entry name.
Protocol: Monitoring method; choose from the dropdown.
- ICMP: Ping the target host to verify reachability.
- TCP: Check reachability via TCP; enter Port when selected.
Target Host: IP address or hostname to monitor.
Port: TCP port; shown only for TCP protocol.
Check Interval (min): Interval between checks.
Failure Count: Consecutive failures before triggering action.
Command
Run Command on Failure: When enabled, runs the command below on failure.
Recheck Delay (min): Minutes after running the command before monitoring resumes.
Command: Action on failure (e.g., reboot outlet).
Targets
Select outlets this command applies to (Outlet1–Outlet6).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the list.
btn:blue:Save: Saves settings and returns to the list.
4-3-2 Edit Ping Monitor
Click an item in the list to open the edit screen.

Field Descriptions
General
Name: Monitor entry name.
Protocol: Monitoring method; choose from the dropdown.
- ICMP: Ping the target host to verify reachability.
- TCP: Check reachability via TCP; enter Port when selected.
Target Host: IP address or hostname to monitor.
Port: TCP port; shown only for TCP protocol.
Check Interval (min): Interval between checks.
Failure Count: Consecutive failures before triggering action.
Command
Run Command on Failure: When enabled, runs the command below on failure.
Recheck Delay (min): Minutes after running the command before monitoring resumes.
Command: Action on failure (e.g., reboot outlet).
Targets
Select outlets this command applies to (Outlet1–Outlet6).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the list.
btn:blue:Save: Saves changes and returns to the list.
Delete
Click btn:red:Delete on the right of a list item to open a confirmation dialog.

btn:gray:Cancel: Closes the dialog without deleting.
btn:red:OK: Confirms deletion of this ping monitor entry.
Chapter 5 Logs and Notifications
This chapter explains how to configure alarm and event notifications.
5-1 Event History
Navigation: History → Event History.
This menu provides event history for system operations, device actions, and alerts.
Query Field Descriptions
| Level | Select event levels to query (multiple selection).
|
| Peripheral Name | Enter keywords to filter peripherals or event content; partial match supported. |
| Start Time | Query start time; leave blank for no start limit. |
| End Time | Query end time; leave blank for no end limit. |
Button Descriptions
btn:green:Filter: Re-queries the event list by level, keyword, and time range.
btn:blue:Export All: Exports all matching events as a CSV download.
btn:gray:Export Page: Exports only events on the current page as CSV.

Event List Field Descriptions
After querying, matching events appear in the list on the right. Column descriptions:
Level Icon: Event severity matching Info, Success, Warning, and Error in the query area.
Time: Event date and time (format per time format under System → System Parameters).
Account and Source IP: Shows the user and source in [account] [IP address] format (e.g., [admin] [192.168.1.213]).
Description: Brief event description (e.g., Login, alert text, or operation record).
5-2 Notification List
Navigation: Notifications → Notification List.
This page lists notification methods and recipients.
Field Descriptions
Notify Method: Alert delivery channel (e.g., All, email) when conditions match.
Recipients: User accounts receiving notifications; each must have a valid email in user settings.
Button Descriptions
btn:blue:Add: Opens the form to add a notification rule.
5-2-1 Add Notification
Click btn:blue:Add to open the form below.

Field Descriptions
Device
| Level | Select alert levels that trigger this notification rule (multiple selection).
|
| Type | Select peripheral or device type; **All** means no type filter. |
Notification
Email: When enabled, sends alert notifications by email.
Pushover: When enabled, sends notifications via Pushover (configure under Engineering first).
Users
Select users to notify; each must have a valid email address.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the notification list.
btn:blue:Save: Saves the notification rule and returns to the list.
5-2-2 Edit Notification
Click an item in the list to open the edit screen.
Field Descriptions
Device
| Level | Select alert levels that trigger this notification rule (multiple selection).
|
| Type | Select peripheral or device type; **All** means no type filter. |
Notification
Email: When enabled, sends alert notifications by email.
Pushover: When enabled, sends notifications via Pushover (configure under Engineering first).
Users
Select users to notify; each must have a valid email address.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the notification list.
btn:blue:Save: Saves the notification rule and returns to the list.
5-2-3 Delete Notification
Click btn:red:Delete on the right of a list item to open a confirmation dialog.

Button Descriptions
btn:gray:Cancel: Cancels deletion and closes the dialog.
btn:red:OK: Confirms deletion of this notification rule.
Chapter 6 Accounts and Security
Manage user accounts, permissions, and security settings.
6-1 User Accounts
Navigation: Permissions → Users (submenu may show "Users").
This page lists all accounts with email, user level, and status.
Field Descriptions
Account: Web UI login account name.
Email: User email for alerts and system messages.
Level: Permission level (e.g., System Administrator, Administrator, Viewer) determining accessible menus and actions.
Status: Account status (e.g., Normal, Locked); abnormal status may block login.
Button Descriptions
btn:blue:Add: Opens the form to create a user account.
6-1-1 Add User
Click btn:blue:Add to open the form below.
Field Descriptions
Level: User permission level (System Administrator, Administrator, Viewer); see permission level reference in this chapter.
Account: Web UI login account name.
Full Name: User display name (optional).
Password: Set or change login password.
Confirm Password: Re-enter password for confirmation.
Disabled: When enabled, the account cannot sign in.
Disable Notifications: When enabled, does not send notifications to this user.
Email: User email for alerts and notifications.
Pushover: Pushover user key or identifier (optional).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the user list.
btn:blue:Save: Saves the account and returns to the list.
6-1-2 Edit User
Click an item in the list to open the edit screen.

Field Descriptions
Level: User permission level (System Administrator, Administrator, Viewer); see permission level reference in this chapter.
Account: Web UI login account name.
Full Name: User display name (optional).
Password: Set or change login password.
Confirm Password: Re-enter password for confirmation.
Disabled: When enabled, the account cannot sign in.
Disable Notifications: When enabled, does not send notifications to this user.
Email: User email for alerts and notifications.
Pushover: Pushover user key or identifier (optional).
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the user list.
btn:blue:Save: Saves the account and returns to the list.
Delete
Click btn:red:Delete on the right of a list item (system administrator account cannot be deleted) to open a confirmation dialog.

btn:gray:Cancel: Discards changes and returns to the user list.
btn:red:OK: Confirms deletion of this user account.
6-2 Password Policy
Navigation: Engineering → Password Policy (This section is numbered in chapter 8; the page is under the Engineering menu).
This page sets login password rules for this device. Click btn:blue:Save when finished.

Field Descriptions
Minimum Password Length: Minimum password length (factory default is often 6).
Maximum Password Length: Maximum password length (factory default is often 32).
Require Uppercase: When enabled, new passwords must include at least one uppercase letter.
Require Lowercase: When enabled, new passwords must include at least one lowercase letter.
Require Digit: When enabled, new passwords must include at least one digit.
Require Special Character: When enabled, new passwords must include at least one special character.
Button Descriptions
btn:gray:Cancel: Discards changes and restores password policy from when the page was opened.
btn:blue:Save: Saves password policy; future password changes must meet the new rules.
Chapter 7 System Settings
This chapter covers system settings such as network, network service, time sync, and firewall.
7-1 System Parameters
Navigation: System → System Parameters ("System Parameters" is a sub-page under System).
This page configures Web UI behavior.
Field Descriptions
Device Name: Custom name in the Web UI and some reports to identify multiple devices.
Idle Logout (min): Auto logout after idle minutes; 0 usually disables idle logout.
Time Format: Date/time format for events and UI (e.g., YYYY/MM/DD HH:MM:SS).
Show Device List: Default screen when entering the device URL in a browser. Yes (On) shows the device list first; No (Off) shows the login page directly.
Screen When Entering Device URL
When Show Device List is Yes, entering the device IP shows the device list; click a device to open management.
Field Descriptions
Device Name: Custom name in the Web UI and some reports to identify multiple devices.
IP: Device network address.
Model: Product model.
Version: Firmware version.
When Show Device List is No, entering the device IP opens the login page directly.

7-2 Network
Navigation: System → Network.
This page configures network settings.

Field Descriptions
IPv4
DHCP: When enabled, IPv4 is assigned by DHCP; disable to enter IP, mask, and gateway manually.
MAC: Shows this device's MAC address (read-only) for network management.
IP Address: Sets the device IPv4 address; reconnect to the Web UI with the new IP after changing it.
Subnet Mask: Sets the IPv4 subnet mask defining the LAN range.
Default Gateway: Sets the default gateway for outbound traffic.
DNS Server 1: Primary DNS server for name resolution.
DNS Server 2: Secondary DNS server as backup; may be blank.
IPv6
IPv6 Address: Sets the device IPv6 address.
Prefix Length: Sets the IPv6 prefix length (commonly 64).
IPv6 Gateway: Sets the IPv6 default gateway.
IPv6 DNS Server 1: Primary IPv6 DNS server.
IPv6 DNS Server 2: Secondary IPv6 DNS server; may be blank.
Button Descriptions
btn:gray:Cancel: Discards changes and restores values from when the page was opened.
btn:blue:Save: Saves and applies network settings; reconnect with the new address if the IP changed.
7-3 Network Service
Navigation: System → Network Service.
Open System → Network Service from the top menu to configure ICMP, SSH, Let's Encrypt, HTTPS manual certificates, and DDNS. Set DNS server addresses on the Network page (DNS Server 1 and DNS Server 2).

Field Descriptions
Network Service
Disable ICMP Echo: When enabled, the device does not respond to ping (ICMP), reducing scan exposure without affecting Web or SNMP.
Enable SSH: Enables SSH remote shell access; use only on trusted networks with strong passwords.
Let's Encrypt (UACME)
Enable automatic certificate: Enables automatic Let's Encrypt HTTPS certificate request and renewal; requires a resolvable domain and contact email.
Domain: Domain name for Let's Encrypt validation; must resolve to this device's public IP.
Contact email: Email address for Let's Encrypt registration and expiry notices.
btn:blue:Save: Saves and applies Let's Encrypt settings.
btn:orange:Test: Tests whether Let's Encrypt certificate prerequisites are met.
Before You Begin
Before requesting a Let's Encrypt certificate, confirm:
- Domain resolves to an IP address reachable from the Internet
- DNS servers are configured correctly (set DNS Server 1 and DNS Server 2 under System → Network)
- The device can reach the Internet for ACME validation
- Firewall (see 7-6 Firewall) does not block Let's Encrypt validation
- Click btn:orange:Test to verify prerequisites before enabling Enable automatic certificate

HTTPS Manual Certificate
Shows the current HTTPS certificate and lets you upload your own certificate files. This card appears on the same page as Let's Encrypt automatic certificates. After applying a manual certificate, confirm the browser is using the updated certificate.
Status: Current HTTPS certificate status (for example, in use and the related service name).
Subject: Subject of the current certificate, typically including CN (Common Name).
Issuer: Issuer of the current certificate.
Validity: Validity period of the current certificate.
Upload certificate: Select certificate.crt (optionally add ca_bundle.crt). Do not upload private.key.
btn:green:Select files: Selects the certificate files to upload.
btn:blue:Upload and apply: Uploads the selected certificate files and applies them to HTTPS.
Advanced settings: Opens advanced certificate options.
To use an internal CA or your own certificate, upload certificate.crt (optionally add ca_bundle.crt) under HTTPS Manual Certificate. Do not upload private.key.
DDNS
Enable DDNS: When enabled, the device updates the dynamic DNS record so the domain points to the current public IP.
Provider: This screen uses stealthone (sotokara.com).
Domain name (subdomain): The subdomain registered with the provider (for example rpd406); combined with sotokara.com it forms the full hostname.
Check interval (minutes): How often, in minutes, the device checks and updates the DDNS record.
btn:blue:Save: Saves DDNS settings.
btn:orange:Update now: Immediately updates the current public IP with the provider.
7-4 Time Sync
Navigation: System → Time Sync.
This page configures device time, time zone, and NTP servers.

Field Descriptions
Device Time
Time: Current device system time (read-only) to verify NTP or manual sync.
Time Zone: Device time zone; set correctly so event timestamps match local time.
Time Sync
Enable Time Sync Service: When enabled, syncs time with NTP periodically; mutually exclusive with manual sync.
Use Custom Time Server: When enabled, syncs using the server in Server URL.
Server URL: Custom NTP server hostname or IP (default is often pool.ntp.org).
btn:orange:Test: Tests connectivity to the configured NTP server.

Manual Sync
Date: Date for manual sync; disable Enable Time Sync Service first.
Time (Manual Sync): Time for manual sync; use Read to copy the computer's current time.
btn:green:Read: Fills Manual Sync fields with the computer's current date and time.
btn:blue:Sync: Writes manually set date and time to the device; disable automatic time sync first.
7-5 Information
Navigation: System → Information.
This page displays device information.

Field Descriptions
System Information
Product Model: Product model (read-only) for support and maintenance.
Firmware Version: Firmware version (read-only) for comparison before and after upgrade.
Build Number: Shows the firmware build number (read-only) for detailed version comparison.
Hardware Information
CPU Usage: CPU usage percentage (read-only); high values may slow response.
Memory Usage: Memory used and total capacity (read-only).
FLASH Usage: FLASH used and total capacity (read-only); run maintenance cleanup when space is low.
7-6 Firewall
Navigation: System → Firewall.
This page enables the firewall and restricts which IP addresses may connect using blacklist or whitelist mode.
Field Descriptions
Enable Firewall: Enables or disables the firewall.
Blacklist Mode: Listed IPs are blocked; others are allowed.
Whitelist Mode: Only listed IPs may connect; all others are denied.
Enabled: Whether each rule is active.
IP: Source IP to allow or deny (may include a subnet).
Action: Allow or deny behavior for this rule.
Button Descriptions
btn:blue:Add: Adds a firewall rule.
7-6-1 Add Firewall Rule
Click btn:blue:Add to open the form below.
Field Descriptions
Enabled: Whether this rule is active.
Source IP: How to specify the source address; choose from the dropdown.
- Single: A single IP address; enter IP when selected.
- Range: An IP address range; enter Start IP and End IP.
IP: Single source IP; shown only for Single.
Start IP: Range start address; shown only for Range.
End IP: Range end address; shown only for Range.
Action: Choose Allow or Deny.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the list.
btn:blue:Save: Saves the rule and returns to the list.
7-6-2 Edit Firewall Rule
Click an item in the list to open the edit screen.

Field Descriptions
Enabled: Whether this rule is active.
Source IP: How to specify the source address; choose from the dropdown.
- Single: A single IP address; enter IP when selected.
- Range: An IP address range; enter Start IP and End IP.
IP: Single source IP; shown only for Single.
Start IP: Range start address; shown only for Range.
End IP: Range end address; shown only for Range.
Action: Choose Allow or Deny.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the list.
btn:blue:Save: Saves changes and returns to the list.
Delete
Click btn:red:Delete on the right of a list item to open a confirmation dialog.

btn:gray:Cancel: Closes the dialog without deleting.
btn:red:OK: Confirms deletion of this firewall rule.
Chapter 8 Maintenance, Backup & Restore
This chapter covers backup, restore, maintenance, and firmware update operations.
8-1 Backup and Restore
Navigation: System → Backup & Restore (or backup under Maintenance, depending on firmware version).
This page backs up and restores device parameters.

Parameter Backup
Back up system parameters and download the file to your computer.
btn:blue:Backup: Exports current device parameters to a file and downloads it.
Parameter Restore
btn:green:Select File: Selects a previously backed-up parameter file to restore.
btn:blue:Restore: Uploads a parameter file and overwrites device settings; back up current settings first.
Backup Contents
Backup files mainly contain configuration settings (alert thresholds, schedules, notification rules, SNMP, network services, engineering parameters, etc.). The following are usually not included and must be reconfigured or verified after restore:
- Historical events and statistics
- User account passwords (verify Users and login credentials after restore)
- Firmware version (restore does not upgrade or downgrade firmware)
- Network IP address (if the backup includes network settings, the IP may change after restore—reconnect using the new address)
8-2 System Maintenance
Navigation: System → Maintenance.
This page sets debug levels, downloads debug logs, and provides system maintenance. Debug levels are for technical troubleshooting; normal operation needs no changes—the factory default is Off for all modules.

Field Descriptions
Debug Information
Each module can be configured independently. When a level is selected, the system logs that level and more severe levels (from most to least severe: Critical → Error → Alert → Info → Debug → Trace; see Debug Level Reference below).
System Control: Log threshold for system core and services (startup, config apply, internal state).
User Manager: Log threshold for login, accounts, and permissions.
Notification Manager: Log threshold for alerts, email, and Pushover delivery.
Hardware Control: Log threshold for sensors, outlet control, and hardware communication.
History: Log threshold for event and history data writes.
Tasks: Log threshold for background and periodic tasks.
Debug Level Reference
| Off | Does not log debug messages for this module; recommended for normal operation. |
| Critical | Logs only severe events that may cause service interruption or data anomalies. |
| Error | Logs error and critical messages (e.g., operation failures, communication errors). |
| Alert | Logs alert, error, and critical messages (e.g., recoverable anomalies or unexpected states). |
| Info | Logs routine operational messages and more severe levels (e.g., main process execution records). |
| Debug | Logs debug details and more severe levels; commonly used for troubleshooting, but log volume increases significantly. |
| Trace | Logs the most detailed trace messages; enable briefly only when directed by technical support, then set back to Off. |
Usage Recommendations
- Troubleshooting workflow: As directed by support, raise only relevant modules (e.g., System Control for network issues, Hardware Control for sensor issues), reproduce the issue, click btn:blue:Download Debug Log, send the file to support, then set levels back to Off.
- Performance and storage: Debug or Trace increases log frequency and FLASH usage and may slightly affect response time. If FLASH usage on the Information page is high, click btn:red:Free Space.
- Difference from Event History: History is for operators to query actions and alerts; debug logs on this page are for internal diagnostics and are technical—most users do not need them.
btn:blue:Download Debug Log: Downloads packaged debug logs from all modules (usually a compressed file) for support analysis; download immediately after reproducing the issue.
System Maintenance
btn:red:Free Space: Clears accumulated debug logs to free FLASH space; does not affect alerts, accounts, or general configuration.
btn:red:Reboot Device: Reboots the device; active connections will drop briefly.
8-3 Firmware Update
Navigation: Engineering → Firmware Update(Same page as Engineering → Firmware Update; this section provides the full procedure.)
This page provides firmware update and factory reset.

Firmware Update
Product Model: Shows the product model (read-only). Verify the firmware file matches this model before upgrading.
Firmware Version: Shows the current firmware version (read-only). Updates after a successful upgrade.
Build Number: Shows the firmware build number (read-only) for detailed version comparison.
Procedure
Firmware update procedure:
Click btn:green:Select File.
Browse to the firmware file and select it.
The selected file name appears below the Select File button.
Click btn:blue:Update to upload, verify, and apply the firmware.
Warning: This device updates offline. The Web UI may be unavailable for about 3–7 minutes. Do not power off or disconnect the network during the upgrade.
btn:green:Select File: Select a firmware file from the local computer (extension per product specification).
btn:blue:Update: Upload and apply firmware; do not power off or disconnect the network during the process.
Factory Reset
Restore all device parameters to factory defaults. All configuration will be erased.
Procedure
Click btn:red:Factory Reset.
Confirm the dialog with btn:red:OK; the device reboots and clears all settings.

After reboot, sign in with factory default admin / admin (see 3-3 Login).
The system requires a password change; set a new password per policy and click btn:blue:OK.
btn:red:Factory Reset: Restore factory defaults; this cannot be undone—back up configuration first.
btn:red:OK: Confirms factory reset and device reboot.
btn:gray:Cancel: Close the dialog without resetting.
Chapter 9 Engineering Mode
Advanced settings for administrators. Open from the top menu Engineering. This chapter includes:
- LDAP: Directory-service login authentication
- RADIUS / TACACS+: External authentication servers
- SNMP Agent: SNMP monitoring and management
- Mail Server: SMTP and test mail
- Alert Service: External notifications such as Pushover
- Syslog: Syslog server and forwarding
9-1 LDAP
Navigation: Engineering → LDAP.
This page configures and tests LDAP.

Field Descriptions
Enable LDAP: When enabled, login validates against LDAP; when disabled, local accounts only.
Server Address: LDAP server hostname or IP.
Port: LDAP port (commonly 389; 636 with SSL).
Enable SSL: When enabled, uses LDAPS encryption for credential transport.
Bind DN: Bind DN for LDAP connection and queries.
Password: Password for the Bind DN. When already set, the field shows eight asterisks (********); submitting those eight asterisks on save means the existing password is not changed.
Base DN: Base DN for user search.
User ID Attribute: LDAP attribute matching login names (commonly uid or sAMAccountName).
Fall Back to Local Password When LDAP Unavailable: When enabled, uses local credentials if LDAP is unreachable, avoiding login lockout.
Permissions and Account Mapping
LDAP only validates credentials. After authentication, access is determined by the Level (System Administrator, Administrator, Viewer) of the matching account name in Permissions → Users. Create a local account matching the LDAP login name and assign a level first; without it, expected permissions may not apply.
9-1-1 LDAP Test
Procedure
Press btn:orange:Test to open the test window; fill in the account and password and press btn:blue:Test. The LDAP test results will be displayed in the result area.

Field Descriptions
Test Username: Enter the LDAP account to be verified to test whether the binding and search are successful.
Test Password: Enter the password for this LDAP account.
Result: Displays LDAP connection and authentication result messages for debugging settings.
Button Descriptions
btn:gray:Close: Close the LDAP test dialog box.
btn:blue:Test: Performs an LDAP authentication test using the entered password.
btn:green:Copy: Copy the test result text to the clipboard.
9-2 RADIUS / TACACS+
Navigation: Engineering → RADIUS / TACACS+.
This screen configures a RADIUS or TACACS+ server so that Web UI logins are authenticated by an external service.

Field Descriptions
Enable RADIUS / Enable TACACS+: When enabled, login authenticates against the corresponding server; when disabled, only local accounts are used.
Server Address: IP or FQDN of the authentication server.
Port: Authentication service port (commonly 1812 for RADIUS and 49 for TACACS+).
Key: The shared key agreed with the authentication server. When already set, the field shows eight asterisks (********); submitting those eight asterisks on save means the existing key is not changed.
Timeout: Seconds to wait for a server response.
Maximum retries: Number of retries when the connection fails.
Fall back to local password when unable to connect: When the server cannot be reached, whether local accounts may be used to log in.
Permissions and Account Mapping
RADIUS / TACACS+ authenticates accounts against an external server. After authentication, access is determined by the Level of the matching account name in Permissions → Users. Create a local account with the same remote login name and assign a level first. To map permissions from server groups, configure the correspondence between RADIUS/TACACS+ groups and local account levels.
Button Descriptions
btn:gray:Cancel: Discards this change.
btn:blue:Save: Saves RADIUS / TACACS+ settings.
btn:orange:Test: Tests connectivity with the authentication server.
9-2-1 RADIUS / TACACS+ Test
Procedure
Click btn:orange:Test on the RADIUS or TACACS+ card to open the test window (titled "Test RADIUS" or "Test TACACS+"). Enter the account and password, then click btn:blue:Test. Results appear in the result area.

Field Descriptions
Test Username: Account used to test authentication against the RADIUS / TACACS+ server.
Test Password: Password for that account.
Result: Connection and authentication result messages for debugging.
Button Descriptions
btn:gray:Close: Closes the test window.
btn:blue:Test: Runs the authentication test with the entered credentials.
btn:green:Copy: Copies the result text to the clipboard.
9-3 SNMP Agent
Navigation: Engineering → SNMP Agent.

This page configures SNMP v1/v2c and v3 Agent settings. SNMP lets NMS tools actively poll device status via MIBs; for proactive alerts, configure Notifications, Syslog, or email/Pushover. For trap OIDs, see the MIB file from btn:blue:Download MIB.
Field Descriptions
SNMP Device Information
Device Name: Shown as sysName in SNMP tools; use a recognizable name.
Device Contact: Shown as SNMP sysContact; enter owner or department contact.
Device Location: Shown as SNMP sysLocation; enter rack or room location.
btn:blue:Download MIB: Downloads this device's MIB for SNMP management tools.
SNMP v1/v2c
Enable SNMP v1/v2c: Enables SNMP v1/v2c Agent; management tools cannot access v1/v2c when disabled.
Read Community: SNMP v1/v2c read community string (default is often public); must match the manager.
SNMP Write: Enables SNMP Set; use only on trusted networks.
Write Community: SNMP v1/v2c write community string (default is often private).
SNMP v3
Enable SNMP v3: Enables SNMP v3 Agent with stronger authentication and encryption.
Username: SNMP v3 login name; must match the manager.
Type: Account permission type: read-only or read-write.
Auth Type: SNMP v3 authentication algorithm (MD5 or SHA).
Auth Password: SNMP v3 authentication password. When already set, the field shows eight asterisks (********); submitting those eight asterisks on save means the existing password is not changed.
Privacy Type: SNMP v3 packet encryption; None means no payload encryption.
Privacy Password: Privacy password when using DES or other encryption. When already set, the field shows eight asterisks (********); submitting those eight asterisks on save means the existing password is not changed.
Button Descriptions
btn:gray:Cancel: Discards changes and restores SNMP settings from when the page was opened.
btn:blue:Save: Saves and applies SNMP settings.
9-4 Mail Server
Navigation: Engineering → Mail Server.
This page configures the mail server and related settings.

Field Descriptions
Mail Delivery Method: Send alerts and notifications via SMTP mail server.
Server Address: SMTP server hostname or IP.
Port: SMTP port (commonly 25, 465, or 587, depending on encryption).
Encryption: Transport encryption: None, SSL, or TLS; must match the mail server.
Sender: From address recipients see.
Authentication: When enabled, requires SMTP account and password.
Account: SMTP authentication account (usually full email address).
Password: SMTP authentication password. When already set, the field shows eight asterisks (********); submitting those eight asterisks on save means the existing password is not changed.
Subject: Default subject prefix for alert emails.
9-4-1 Test Mail
Procedure
Press btn:orange:Test to open the test window; after filling in the email and content to be tested, press btn:blue:Test to send, and the results will be displayed in the result area.

Field Descriptions
Recipient Email: The recipient email of the test email. It is recommended to send it to yourself for confirmation first.
Content: Test email content, you can leave it blank or use the default test text.
Result: Displays the success or failure message for checking the SMTP settings.
Button Descriptions
btn:gray:Close: Close the test email dialog box.
btn:blue:Test: Send a test email based on the current SMTP settings.
btn:green:Copy: Copy the test results to the clipboard.
9-5 Alert Service
Navigation: Engineering → Alert Service.
This page configures the alert server and Pushover settings.

Field Descriptions
Alert Server
Language: Display language for Pushover and other alert messages; choose from the dropdown (default English).
- English
- Traditional Chinese
Pushover
Pushover is a third-party push notification service. Before configuring, register at the Pushover website and create an application:
- After signing in to Pushover, copy your User Key from Your User Key
- Create an Application and copy its API Token
API Token: Pushover application API Token from the Pushover website.
Title: Title text shown in push messages.
User Key: Pushover User Key determining which device receives messages.
btn:blue:Website: Opens the Pushover website to look up or request API Token and User Key.
btn:orange:Test: Sends a test push to verify Pushover settings.
9-6 Syslog
Navigation: Engineering → Syslog.
Lists configured Syslog server addresses and ports.
Field Descriptions
Address: Syslog server IP or FQDN; the device sends logs to this host.
Port: Syslog port (UDP default is often 514).
Tag: Custom tag to distinguish devices or purposes on the log server.
Button Descriptions
btn:blue:Add: Opens the form to add a Syslog server.
9-6-1 Add Syslog
Click btn:blue:Add to open the form below.

Field Descriptions
Address: Syslog server IP or FQDN; the device sends logs to this host.
Port: Syslog port (UDP default is often 514).
Tag: Custom tag to distinguish devices or purposes on the log server.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the Syslog list.
btn:blue:Save: Saves Syslog settings and returns to the list.
btn:orange:Test: Sends a Syslog test message.
9-6-2 Edit Syslog
Click an item in the list to open the edit screen.
Field Descriptions
Address: Syslog server IP or FQDN; the device sends logs to this host.
Port: Syslog port (UDP default is often 514).
Tag: Custom tag to distinguish devices or purposes on the log server.
Button Descriptions
btn:gray:Cancel: Discards changes and returns to the Syslog list.
btn:blue:Save: Saves Syslog settings and returns to the list.
btn:orange:Test: Sends a Syslog test message.
Delete
Click btn:red:Delete on the right of a list item to open a confirmation dialog.

btn:gray:Cancel: Discards changes and returns to the Syslog list.
btn:red:OK: Confirms deletion of this Syslog server entry.
Appendix
Factory Reset
If you forget the network account password for this product, use the RESET button to restore the system to factory defaults. The device will also reboot.

Hardware reset (pinhole)
Use a straightened paper clip to press the RESET pinhole on the rear panel (see the figure above; also labeled 6 in 1-4 Hardware Description).
Press and hold RESET for more than 3 seconds until the red LED starts flashing. Release within 3–10 seconds to reset the admin password to the factory default admin and obtain an IP via DHCP (if no DHCP server is available, the default IP is 192.168.1.100). After reboot, sign in with admin / admin; the system requires a password change (see 3-3 Login).
Press and hold RESET for more than 10 seconds until the LED stays solid. Release to clear all device data.
Web UI reset
Alternatively, an administrator can restore defaults from Engineering → Firmware Update in the web UI (see 8-3 Firmware Update). After reset, network settings return to factory defaults and the default administrator account is restored.

Click btn:red:Factory Reset.
Confirm the dialog with btn:red:OK; the device reboots and clears all settings.

After reboot, sign in with factory default admin / admin (see 3-3 Login).
The system requires a password change; set a new password per policy and click btn:blue:OK.
Warranty
This product is warranted for one year from the date of purchase against defects in materials and workmanship. If a problem occurs during the warranty period, contact your dealer for repair or replacement. Refunds are not provided. Requests for factory repair without original proof of purchase cannot be processed.
When returning this product for factory service, pack it in the original packaging, or packaging that provides equivalent protection. The package must include proof of purchase, and the RMA number must be clearly marked on the outside.
If the serial number label provided by the manufacturer has been removed or altered, this warranty is void.
This warranty does not cover cosmetic damage, or damage caused by acts of nature, accident, misuse, abuse, or unauthorized modification of any part of the product. It also does not cover damage caused by improper operation or maintenance, connection to unsuitable equipment, or repair attempts by non-authorized personnel. This warranty does not apply to products resold in "as is" or defective condition.
Under no circumstances shall the company's liability exceed the purchase price paid for this product. The company is not liable for any direct, indirect, special, incidental, or consequential damages arising from the use of this product, software, or documentation, including but not limited to loss of data, loss of profits, downtime, loss of goodwill, damage to equipment or property, or costs of replacement, recovery, or reconstruction of programs and data.
The company makes no warranties, express, implied, or statutory, regarding the product, documentation, intended use, or bundled software, and specifically disclaims warranties of quality, performance, merchantability, or fitness for a particular purpose.
The company reserves the right to modify or update this product, software, or documentation without prior notice to any individual or entity.
For more information about extended warranty options, contact your dealer.




